Features
|
|
|
¥
|
Compact construction
|
|
¥
|
Simple re-lamping with standard
lamps
|
|
¥
|
Directional control with pivot
bracket
|
|
¥
|
Extensive lamp options including
400w MBI
|
|
¥
|
Indirect entries and terminals for
looping
|
|
Certification &
Approval
|
|
Certification Code:
|
EEx de IIB T2 to T6 (Dependent on lamp source - see data)
|
|
Certification Standard:
|
BS5501 Parts 1, 5 and 6 (EN50014-018-019)
|
|
Certificate Number:
|
SIRA Ex 94C 1043
|
|
Degree of Protection:
|
IP 66 to IEC 529
|
Technical Data
|
Supply voltage
|
Standard product 240v, 50 Hz.
Other voltages and frequencies on request.
|
|
Control gear
|
Integral within the luminaire.
Operating power factor
SON and MBI min. 0.8. HPMV min. 0.9.
|
|
Lamp source options
|
Certified with elliptical lamps.
400w SON T3 @ Ta = 550C
T4 @ Ta = 400C (v)
400w SON R T3 @ Ta = 550C
400w MBI T3 @ Ta = 550C
T4 @ Ta = 400C (v)
400w HPMVMBF T3 @ Ta = 550C
All with GES (E40) lampholder.
Lamps are not included.
Standard temperature classification applies to all
methods of mounting.
A (v) indicates an improved temperature classification if
mounted vertically.
|
|
Mounting facilities
|
Fixed strap as standard. Pendant or pivot bracket
available.
|
|
Cable entries
|
2 x M 20 - ISO (1 plugged) as standard. Other thread
forms available.
|
|
Terminals
|
4 wire and Earth with looping facility. Cable size 4
mm2 max.
|
|
Operating temperature
|
-20°C to +55°C as standard.
|
|
Reflector
|
Internal polished aluminium. External reflector available
at extra cost.
|
|
Access for lamp change
|
Removable wellglass with tapered spigot flamepath for
easy access.
Internal flamepath construction with full gasket
protection.
|
|
Access for connections
|
Removable EEx e terminal cover with 4 stainless steel
screws.
|
|
Finish
|
2 pack aqua epoxy paint on pre-treated & primed
surface.
Alternative finishes available.
|
|
Material
|
Corrosion resistant light alloy to BS1490. LG2 gunmetal
or 316 stainless steel options at extra cost.
|
|
Protective guard
|
Wire guard available at extra cost.
|
|
Weight
|
Standard
|
SON & MBI
|
30 kg
|
|
|
|
HPMV
|
29 kg
|
How To Order
Product codes are formed as follows:
|
Series Ref.
|
Lamp Size & Type
|
Voltage
|
Frequency
|
|
630
|
e.g. 400W SON
|
e.g. 240
|
e.g. 50
|
and written: 630 / 400W SON / 240 / 50
Special features are specified
using the following codes:
|
/Pg
|
Pg 16 cable entries
|
|
/WG
|
Wire Guard
|
|
/R
|
External Reflector
|
|
/PB
|
Pivot Bracket
|
|
/P
|
Pendant mounting
|
These are added to the product codes as
required:
e.g. 630 / 400W SON / 240 / 50 / Pg / WG
Please contact PFP for any technical advice you may require
including photometric details.
A technical design service is available for all our customers.
Tel: +44 (0) 121 783 7161 Fax: + (0) 121 783 5717 Email: